KORAFLEX Thin FKT

lowest construction depth

KORAFLEX Thin FKT is a trench heater with the lowest unit height. It is particularly suited to interiors with low floor depth and as a secondary heating unit for shielding cold from French windows.

ECONOMIC – black lacquered galvanized steel casing, non-lacquered heat exchanger
EXCLUSIVE – black lacquered galvanized steel casing, RAL 9005 black lacquered heat exchanger

KORAFLEX – Discover What We Can Do                                   KORAFLEX - If You Want More…
  • Heating
  • Natural convection
  • Higher performance
  • Low energy consumption
ECONOMIC version   non-lacquered heat exchanger
EXCLUSIVE version  RAL 9005 black lacquered heat exchanger
Depth [mm] 60 mm
Width [mm] 140, 200, 260, 320 mm
Length [mm] 800 to 3 000 mm (by 100 mm)
Heat output [W] from 43 to 644 W
Max. operating pressure [MPa] 1.2 MPa
Max. operating temperature [°C] 90 °C
Connecting thread inner G ½"
Cover grilles
Thin trench heaters may only be fitted with Thin grilles, and
after casing modifications Cross grilles.
No other grilles are available for this range.
PM Thin

info
Where a left-hand connection to the heating system is required, rotate the heat exchanger in the trench heater by 180°.
The design of the trench heater casing does not allow substituting Thin and Cross grilles after ordering.
Note, please, that grilles must be ordered together with the trench heaters, as the casing must undergo alternation.​
Thin grilles are not available in linear design.

Heat output [W] where t1/t2/ti EN 442. Measurements are shown in mm, including Thin-frame.


ΔT = 50 °C Length [mm] Temperature exponent
Depth
[mm]
Width
[mm]
800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000
60 140 43 53 63 73 83 93 104 114 124 134 144 154 164 175 185 195 205 215 225 235 246 256 266 1,3030
60 200 87 105 122 139 156 173 190 207 224 242 259 276 293 310 327 344 362 379 396 413 430 447 464 1,5168
60 260 100 120 139 159 179 198 218 238 257 277 296 316 336 355 375 395 414 434 454 473 493 512 532 1,7953
60 320 114 138 162 186 210 234 258 282 306 331 355 379 403 427 451 475 499 523 548 572 596 620 644 1,6785
Standard contents
​ RAL 9005 black lacquered galvanized steel casing
​ Economic – non-lacquered Al/Cu heat exchanger with bleed valve
​ Exclusive – RAL 9005 black lacquered Al/Cu heat exchanger with bleed valve
​ aluminium T-frame for Thin grille, silver elox
​ metal cover plate
​ levelling set screws and 4 anchors
​ spacers for correct installation and concreting
​ hardboard cover to protect trench heater from contamination
​ durable packaging, installation instructions
 
Optional accessories
​ Thin roll-up cover grille of your choice
​ Cross cover grille – design solution, must be ordered together with the trench heater
​ aluminium frame for Thin grille, available in light / dark bronze elox, black elox or lacquered                  according to the RAL colour chart
​ regulating valve set, angle or straight
​ thermostatic valve, angle, straight or axial 
​ thermostatic pressure-independent valve, angle, straight or axial 
​ brass elbow ½" × ½" 90° 
​ stainless steel flexible hoses 
​ thermoelectric actuator TEP 230 or TEP 24 
​ SIEMENS thermostat RAA21 or RDE 100.1
​ thermostatic head with capillary tube 
​ 24 V DC power supply unit 
​ OSB cover board with increased stiffness for installation purposes
TRENCH HEATER COMPONENTS
Složení konvektoru FK_1

 

1black lacquered galvanized steel casing
2choice of grille (please order separately)
3choice of aluminium frame
4Al/Cu heat exchanger
54 anchors
6levelling set screws
7metal cover plate
8brackets
9spacers for correct installation and concreting
Suitable grilles 
FRAMES
EN_Thin_PM Standard Thin grille frame     Optional Cross grille frame (upon request)
Thin rámečky
KORAFLEX  THIN FKT  -  PRODUCT RANGE 
DEPTH 60 mm
FKT - sirky
Typ 60/140
Typ 60/200
Thin typ 140 Thin typ 200
Typ 60/260
Typ 60/320
Thin typ 260 Thin typ 320
info  Measurements shown in mm. The given widths of trench heaters are identical for both models fitted with Thin or Cross grille frames.
​FK TRENCH HEATER INSTALLATION
Construction recommendations

To ensure correct operation, it is essential that the following principles are respected.

A properly installed trench heater must be positioned horizontally, with the heat exchanger oriented towards the window. The trench heater casing must have straight, non-deformed upper edges to ensure correct operation of the cover grille.

Installation of the trench heater is possible
• in a concrete floor (standard construction solution)
• in a plinth – for renovations or additional modifications
• in raised floors – using special supports designed for this purpose - For KORAFLEX Pool (FKP, FVP) installation of raised floor supports is not recommended for design reasons.

In all cases, it is necessary to anchor the trench heater firmly to prevent it from being stepped on and to ensure that all technical installation requirements are met. We recommend leaving the cover plate in place throughout the construction work to prevent contamination of the trench heater’s internal space. A non-walkable hardboard cover is supplied as
standard for basic protection. For installation purposes, an OSB cover with increased rigidity can be ordered as an optional accessory.
  • The recommended installation distance of the trench heater from the window / wall is max. 100 mm.
  • The installation opening should be at least 100 mm larger than the convector dimensions in both length and width.
  • For trench heaters with natural convection (without fan), for lefthand connection to the heating system it is sufficient to rotate the heat exchanger by 180°.
  • When using fixing anchors, the bottom width of the trench heater is increased by 42 mm on each side.
  • During concreting, the trench heater must be levelled horizontally using the levelling set screws and fixed using fixing anchors, which prevents the trench heater from shifting during subsequent concrete pouring.
  • We recommend connecting to the heating system using a lockshield and a thermostatic valve. The connection to the heat exchanger is an inner thread G ½". After connection to the heating system, bleed the trench heater and carry out a pressure test.
  • We recommend thermally insulating the trench heater before installation on the outer longer sides of the casing (e.g. polystyrene) to prevent heat losses into the floor.
  • For trench heaters with a fan, we recommend fixing and sound insulation by pouring lean concrete along the sides and under the bottom of the casing.
  • During concrete pouring, the trench heater must be loaded vertically.
  • During concreting, it is very important to brace the trench heater to prevent longitudinal bending. For this purpose, spacers are installed in the trench heater. After concreting, these spacers can be easily removed.
  • During concrete or anhydrite pouring, thoroughly seal all openings into the trench heater to prevent it from being filled with building material. We also recommend insulating the trench heater casing against moisture.
  • If the trench heater will not be concreted in, we recommend using one of the raised floor installation variants. The standard version of the trench heater is not self-supporting.
  • KORAFLEX Variant F2V and F4V trench heaters with cooling and Pool versions (FKP, FVP) for humid environments are equipped as standard with a built-in condensate or overflow water drain. The F2V 11/20 variant and the Pool version have a drain tube positioned towards the wall. During installation of all the above-mentioned types, it is necessary to connect the tube at the bottom of the trench heater to piping with a secured slope for the drainage of overflow water or condensate. We recommend fitting the drain with an odour trap.
  • The fans are attached to the trench heater casing using magnets. In the stainless steel version, the fans are attached with hook-and-loop fasteners. This system allows the fans to be removed from the trench heater during installation to prevent damage or contamination. During normal operation, they can also be removed in the switched-off state and cleaned. In all model lines except the Pool line, the fans are installed so that the airflow is directed straight towards the window.
  • KORAFLEX Pool (FKP, FVP) trench heaters are designed for use near swimming pools. The separation partition serves to collect water from the pool, but cannot function as a standard pool overflow. This part is always positioned closer to the pool. The heating section with the heat exchanger and fans must always be positioned further from the pool. KORAFLEX Pool is equipped with two drain tubes. Installation, operation and maintenance of these units require special conditions, which can be found on our website or in the installation instructions. Not suitable for saltwater pools.
  • The electrical installation design must be carried out by a person with the appropriate professional qualifications and must comply with the relevant standards.
  • Installation and servicing of the electrical system must be performed by a qualified person with the appropriate electrotechnical qualifications.
  • Before commissioning, an initial inspection of the electrical installation must be carried out in accordance with the applicable standards.
Recommended positioning of heat exchangers in trench heaters
EN_FK_umístění
• Trench heaters should be positioned a maximum of 100 mm from windows. In order to achieve maximum performance, the recommended position for heat exchangers in the trench heater is always on the window side. This results in natural air flow, whereby warm air rises and cool air is drawn into the trench heater. In this way, cool air at the window is screened and the air in the room is heated.

 

 

 

 

TRENCH HEATER INSTALLATION
         FK - montaz konvektoru - 1-bez                              

1 - trench heater with natural convection, 2 - heat exchanger, 3 - grille, 4 - U-frame, 5 - F-frame, 6 - set screws, 7 - anchors, 8 - up to 300mm deep dividing partition, 9 - window,  10 - floor level,  11 - grout,
12 - expansion joint, 13 - insulation, 14 - concrete filler, 15 - sub-floor

Trench heater multiple installations
Casing types according to water connections and lowered sides for multiple installations

EN_FK_instalace  • Lowered trench heater casing sides are used where invisible connections are desired between trench heaters (multiple trench heaters around a room, eg. in administrative buildings, restaurants, hotels, etc.). When ordering grilles, care must be taken to include information in the order code that the grilles required are to be used with trench heaters with lowered faces.

 

 


                                                                                                                                                                                                         

ORDER CODE

Example order code: FKT-100/06/26-V1T1P0

KORAFLEX trench heater with natural convection, Thin model, length 100 cm, depth 6 cm, width 20 cm, counter-flow heat exchanger in Economic version (without surface treatment),
T-frame for Thin grille, silver elox, right-hand connection to heating system, without lowered face.

KORAFLEX
Convection
Thin
 
Length/Depth/Width (cm)
 
Heat exchanger
type
Heat exchanger
colour
Frame
Frame colour
Connection
side
Lowered face
F
K
T
-
100/06/20
-
V
1
U
1
P
0
 
 
 
 
 
 
V counter-flow
P* single-stream
0 without heat
exchanger
1 non-lacquered
5 RAL 9005
9 other colour RAL
0 without heat
exchanger
T for Thin grille
C for Cross grille
0 without frame
1 silver elox
2 dark bronze elox
3 light bronze elox
5 black elox
9 other RAL colour
0 without frame
P - right
0 without lowered face
1 lower face – input side
2 lower face – opposite input side
3 both sides lower

 

   
   
   
P* – single-stream heat exchangers are fitted as standard in trench heaters 140 mm wide.