Can we use cookies,
so that we know how is our website doing?

KORALINE Max LKM 

The exclusive KORALINE Max LKM series of convectors combines high safety and maximum heating output. For increased safety, the casing of KORALINE Max LKM convectors is made of 1.5 mm thick galvanized sheet steel and is also fitted with a symmetric safety pencilproof grille. The grille comprises perforated holes of small dimensions. The grille is locked in the convector preventing easy removal by unauthorised persons. The KORALINE Max series of convectors have a bevelled front edge to prevent potential injury. Heat exchanger bodies are fitted with safety locks to prevent removal by unauthorised persons. This model series also includes high-performance  heat exchangers with double the area of uniquely shaped fins. The KORALINE Max range of convectors is particularly suited to schools, nurseries, hospitals, office or commercial premises and wherever there is a need to combine safety with high heat output and design.

Height [mm] 230, 300, 400, 500, 600, 700, 800 mm
Width [mm] 80, 130, 180, 230 mm
Length [mm] 600, 700, 800, 900, 1 000, 1 100, 1 200, 1 400, 1 600, 1 800, 2 000 mm
Output [W] from 220 to 5 096 W
Max. operating pressure [MPa] 1,2 MPa
Max. operating temperature [°C] 90 °C
Surface temperature  [°C] 40 °C According to inlet water temperature
Connecting thread inner G 1/2"
Connection method lower (recommended), side
ΔT = 50 °C Length [mm] Temperature exponent
Width
[mm]
Height
[mm]
600 700 800 900 1000 1100 1200 1400 1600 1800 2000
80 230 220 274 327 380 433 487 540 647 753 860 966 1,326
130 230 405 516 627 738 848 959 1070 1292 1513 1735 1956 1,388
180 230 588 757 926 1096 1265 1434 1604 1942 2281 2620 2959 1,411
230 230 802 1021 1240 1459 1678 1897 2116 2554 2992 3430 3868 1,43
80 300 236 292 349 406 463 520 577 691 804 918 1032 1,33
130 300 437 557 676 795 915 1034 1154 1393 1631 1870 2109 1,383
180 300 633 815 997 1179 1362 1544 1726 2091 2455 2820 3185 1,406
230 300 865 1101 1338 1574 1810 2046 2283 2755 3228 3701 4173 1,424
80 400 254 316 377 438 500 561 623 745 868 991 1114 1,3353
130 400 470 599 728 856 985 1113 1242 1499 1756 2013 2270 1,3741
180 400 680 876 1072 1268 1464 1660 1856 2247 2639 3031 3423 1,3979
230 400 931 1186 1440 1695 1949 2204 2458 2967 3476 3985 4494 1,4151
80 500 271 337 402 467 533 598 664 795 926 1057 1188 1,3407
130 500 494 630 765 900 1035 1170 1305 1575 1845 2115 2386 1,3657
180 500 714 920 1126 1331 1537 1743 1949 2360 2772 3184 3595 1,39
230 500 979 1247 1514 1782 2049 2317 2585 3120 3655 4190 4725 1,4065
80 600 287 356 425 495 564 633 702 841 979 1118 1256 1,3462
130 600 512 652 791 931 1071 1211 1351 1630 1910 2190 2469 1,3573
180 600 739 952 1165 1378 1591 1804 2017 2443 2869 3295 3721 1,3821
230 600 1014 1291 1568 1845 2122 2399 2676 3230 3784 4338 4892 1,398
80 700 302 375 447 520 593 666 739 885 1030 1176 1322 1,3516
130 700 524 667 811 954 1097 1240 1384 1670 1957 2243 2530 1,3488
180 700 757 976 1194 1412 1630 1848 2067 2503 2940 3376 3813 1,3742
230 700 1039 1323 1606 1890 2174 2458 2742 3309 3877 4444 5012 1,3895
80 800 316 393 469 545 622 698 774 927 1080 1233 1385 1,357
130 800 533 679 824 970 1115 1261 1407 1698 1989 2280 2572 1,3404
180 800 770 992 1214 1436 1658 1880 2102 2546 2990 3434 3878 1,3662
230 800 1056 1345 1633 1922 2210 2499 2787 3364 3942 4519 5096 1,381

​Convector composition KORALINE MAX LKM


KORALINE Safe_Max
                                                          

Standard contents

1symmetric safety pencilproof grille
2 galvanized steel casing
3 fixed side cover in casing colour
4 axial thermostatic valve
5 extension nipple for convectors from 150 mm in height
6 Al/Cu heat exchanger
7 floor-level brackets
8 transport stopper and bracket mount
9 wall fixing mounts for convectors from 230 mm in height
10 heat exchanger with safety lock

Optional accessories

11 floor-level bracket and connections covers with safety features
12 thermostatic head

*further RAL lacquers for casings and for grilles available
*wall brackets with heat exchanger safety lock
*sub-floor brackets with heat exchanger safety lock
*elbow or straight lockshield
*elbow or straight thermostatic valve
*TEP 230 or TEP 24 thermoelectric actuator
*SIEMENS RAA21 or RDE 100.1 room thermostat
*QAA32 room temperature sensor 
*thermostatic head with incorporated control and immersion remote sensor

SUMMARY OF TYPES KORALINE Max LKM

Max_46
Max_47

 Measurements in mm. Alterations to technical specifications reserved.

  Floor-level bracket height above floor level for all KORALINE models is 100 mm. Measurements in mm. Alterations to technical specifications reserved.      

ASSEMBLY 

Installation instructions – installation procedure
The first step is to measure and screw in the brackets. Floor-level brackets contain transport stopper and bracket mount, that allows for easy and stable mounting of heat exchanger onto a bracket. Transport stopper prevents movement and damage of heat exchanger during transport. Floor brackets can be measured out according to the drilling templates included in the package. The heat exchanger is then mounted onto them and connected to the heating system. The heat exchangers must be bled. The last step is to fit the convector casing with the grille and attach it to the brackets. The grilles on Optimal, Power, Safe and Max free-standing convectors are removable for easier cleaning and maintenance. For more detailed information on each KORALINE type, please refer to the installation instructions. The units are supplied assembled, except for the brackets and mounts, valves and extension nipples, if applicable, which are included separately with the product.

BRACKETS AND MOUNTS

KORALINE free-standing convectors are fitted with floor-level brackets and some higher models also with wall fixing mounts as standard (see the Standard contents list at each model line). Sub-floor brackets and wall brackets are available upon request.
Floor-level brackets - fitted as standard

KORALINE free-standing convectors 2,000 mm in length and above are supplied with a central bracket for greater stability
For a correct installation of floor-level brackets it is necessary to use transport stopper and bracket mount that also holds heat exchanger in place during transport
Stojánky na čistou podlahu

Floor-level bracket height above floor level for all KORALINE models is 100 mm.

Floor-level bracket casing - optional accessory

Floor-level bracket casings are designed to cover connections and the edges of floor-level brackets, and must be ordered in pairs.

 

bez zakrytování

Kryt připojení z rozpadu

 

Zakrytování

 Floor-level bracket without bracket casing Floor-level bracket casing Floor-level bracket casing installation
Sub-floor brackets - optional accessory

Stojanky na hrubou podlahu

Lengths over 2 000 mm – three brackets for increased stability

Wall brackets  - optional accessory                            

Konzole na zeď

When mounting convectors on walls, the distance between the unit and the wall  25–45 mm lengths over 2 000 mm – three brackets for increased stability

 Wall fixing mounts - Safe and Max models

– from 230 mm in height

              koraline_stenova_fixace_lks                                     

Included as standard for higher convectors according to height of given model. When mounting convectors on walls, the distance between the unit and the wall is 25–45 mm

Montáž_54

Montáž_55

ORDER CODE

Example order code: LKM-140/23/18-V1SP0-10

KORALINE Max free-standing convector, Length 140 cm, Height 23 cm, Width 18 cm, Steel casing white RAL 9016, symmetric safety pencilproof grille in casing colour.

KORALINE

Natural

convection

Type   Length/Height/Width (cm)  

Convector

connection

Heat

exchanger
colour

Material

used 

Grille

type

Grille 

colour

 

Casing

colour

L K M - 140/23/18 - V 1 S P 0 - 10

 

 

Max

 

 

 

counter-flow
 

without colour 

steel

perforated

casing colour

 

10 RAL 9016

** see colour chart Licon

99 other RAL colour 

Contact form

For more information, don't hesitate to contact us.

Read about how we handle your general data.