KORALINE Combi LKC
KORALINE Combi LKC free-standing convectors are equipped with a high-performance heat exchanger with double fin area. The safety grille is perforated directly into the galvanized steel casing of the convectors making it an integral part of the convectors. The design and dimensions of the heat exchanger ensure highly efficient heat transfer. The entire model series achieves higher heat outputs. With more compact dimensions, maximum output and low surface temperature of the casing, these convectors are designed to be used heating domestic homes, modern office buildings, commercial spaces and other large-scale projects.
Height [mm] | 230, 300, 400, 500 mm |
Width [mm] | 130, 180, 230 mm |
Length [mm] | 600, 700, 800, 900, 1 000, 1 100, 1 200, 1 400, 1 600, 1 800, 2 000, 2 200, 2 400, 2 600, 2 800, 3 000 mm |
Output [W] | from 405 to 7 400 W |
Max. operating pressure [MPa] | 1,2 MPa |
Max. operating temperature [°C] | 110 °C |
Max. surface temperature [°C] | 40 °C |
Connecting thread | inner G 1/2" |
Connecting method | lower (recommended), side |
ΔT = 50 °C | Length [mm] | Temperature exponent | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Width [mm] | Height [mm] | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 | 1400 | 1600 | 1800 | 2000 | 2200 | 2400 | 2600 | 2800 | 3000 | |
130 | 230 | 405 | 516 | 627 | 738 | 848 | 959 | 1070 | 1292 | 1513 | 1735 | 1956 | 2178 | 2399 | 2621 | 2842 | 3064 | 1,388 |
180 | 230 | 588 | 757 | 926 | 1096 | 1265 | 1434 | 1604 | 1942 | 2281 | 2620 | 2959 | 3297 | 3636 | 3975 | 4313 | 4652 | 1,411 |
230 | 230 | 802 | 1021 | 1240 | 1459 | 1678 | 1897 | 2116 | 2554 | 2992 | 3430 | 3868 | 4306 | 4744 | 5182 | 5621 | 6059 | 1,43 |
130 | 300 | 437 | 557 | 676 | 795 | 915 | 1034 | 1154 | 1393 | 1631 | 1870 | 2109 | 2348 | 2587 | 2826 | 3065 | 3303 | 1,383 |
180 | 300 | 633 | 815 | 997 | 1179 | 1362 | 1544 | 1726 | 2091 | 2455 | 2820 | 3185 | 3549 | 3914 | 4278 | 4643 | 5007 | 1,406 |
230 | 300 | 865 | 1101 | 1338 | 1574 | 1810 | 2046 | 2283 | 2755 | 3228 | 3701 | 4173 | 4646 | 5119 | 5591 | 6064 | 6536 | 1,424 |
130 | 400 | 470 | 599 | 728 | 856 | 985 | 1113 | 1242 | 1499 | 1756 | 2013 | 2270 | 2527 | 2784 | 3041 | 3298 | 3556 | 1,3741 |
180 | 400 | 680 | 876 | 1072 | 1268 | 1464 | 1660 | 1856 | 2247 | 2639 | 3031 | 3423 | 3815 | 4207 | 4599 | 4990 | 5382 | 1,3979 |
230 | 400 | 931 | 1186 | 1440 | 1695 | 1949 | 2204 | 2458 | 2967 | 3476 | 3985 | 4494 | 5003 | 5512 | 6021 | 6530 | 7039 | 1,4151 |
130 | 500 | 494 | 630 | 765 | 900 | 1035 | 1170 | 1305 | 1575 | 1845 | 2115 | 2386 | 2656 | 2926 | 3196 | 3466 | 3736 | 1,3657 |
180 | 500 | 714 | 920 | 1126 | 1331 | 1537 | 1743 | 1949 | 2360 | 2772 | 3184 | 3595 | 4007 | 4418 | 4830 | 5241 | 5653 | 1,39 |
230 | 500 | 979 | 1247 | 1514 | 1782 | 2049 | 2317 | 2585 | 3120 | 3655 | 4190 | 4725 | 5260 | 5795 | 6330 | 6865 | 7400 | 1,4065 |
Convector composition KORALINE Combi LKC
| Standard contents1 galvanized steel casing incorporating perforated safety grille, lacquered white RAL 9016 *assembly instructions and durable packaging Optional accessories8 floor-level bracket casings 9 thermostatic head *further RAL lacquers for casings available |
ASSEMBLY
Installation instructions – installation procedure
The first step is to measure and screw in the brackets. Floor brackets can be measured out according to the drilling templates included in the package. The heat exchanger is then mounted onto them and connected to the heating system. The heat exchangers must be bled. The last step is to fit the convector casing with the grille and attach it to the brackets. The grilles on Optimal, Power, Safe and Max free-standing convectors are removable for easier cleaning and maintenance. For more detailed information on each KORALINE type, please refer to the installation instructions. The units are supplied assembled, except for the brackets and mounts, valves and extension nipples, if applicable, which are included separately with the product.
BRACKETS AND MOUNTS
KORALINE free-standing convectors are fitted with floor-level brackets and some higher models also with wall fixing mounts as standard (see the Standard contents list at each model line). Sub-floor brackets and wall brackets are available upon request.
Floor-level brackets - fitted as standard
KORALINE free-standing convectors 2,000 mm in length and above are supplied with a central bracket for greater stability
Floor-level bracket height above floor level for all KORALINE models is 100 mm.
Floor-level bracket casing - optional accessory
Floor-level bracket casings are designed to cover connections and the edges of floor-level brackets, and must be ordered in pairs.
|
| |
Floor-level bracket without bracket casing | Floor-level bracket casing | Floor-level bracket casing installation |
Sub-floor brackets - optional accessory
Lengths over 2 000 mm – three brackets for increased stability
Wall brackets - optional accessory
When mounting convectors on walls, the distance between the unit and the wall 25–45 mm lengths over 2 000 mm – three brackets for increased stability
Wall fixing mounts
Optimal, Power, Basic and Combi models – from 400 mm in height included as standard
Included as standard for higher convectors according to height of given model. When mounting convectors on walls, the distance between the unit and the wall is 25–45 mm.
MOUNTING
ORDER CODE
Example order code: LKC-140/23/18-V1SP0-10
KORALINE Combi free-standing convector, Length 140 cm, Height 23 cm, Width 18 cm, Steel casing and grille white RAL 9016.
KORALINE | Natural convection | Type Combi | Length/Height/Width (cm) | Convector connection | Heat exchanger | Material used | Grille type | Grille colour | Casing colour | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|
L | K | C | - | 140/23/18 | - | V | 1 | S | P | 0 | - | 10 |
|
|
|
|
| counter-flow | without colour | steel | perforated | casing colour |
| 10 RAL 9016 ** see colour chart Licon 99 other RAL colour |
Contact form