FORCED CONVECTION - REGULATION
NATURAL CONVECTION – REGULATION
Regulation of the heating or cooling medium flow forms a central role in the correct control of convector heating output. Correct selection of regulation elements guarantees a comfortable ambient temperature and contributes to heating cost minimalization. Fans and thermoelectric actuators are powered by 24 V DC and the fan speed is operated by 0-10V control voltage.
Standard contents | Optional accessories |
|
|
Installation must be carried out in accordance with valid regulations and safety procedures! The manufacturer cannot be held liable for any defects, damages and injuries caused by improper installation.
KORAFLEX Pool-V FVP
For KORAFLEX Pool-V humid environment trench heaters, the standard control system description applies. The difference lies in placing the FCR-BOX in a pattress box with a higher degree of protection. The fan is equipped with stainless steel casing and its electronics are protected against splashing water. For this model we recommend using a temperature sensor that monitors the temperature in the pool area. The sensor is designed for RDG 160T thermostats. The trench heater is not designed to be permanently flooded with pool water. Please familiarise yourself thoroughly with the warranty conditions and conditions of use.
KORAFLEX Energy FVE
It is powered by 230V AC mains voltage. The switched-mode power supply is situated inside the convector and converts mains voltage to 24 V DC. Fan speed is controlled by 0–10 V DC controlled voltage either from the BMS or the thermostat. Electrical installation design must be carried out by a suitably qualified person and must comply with relevant regulations. Installation and maintenance of the electrical installation must be carried out by a qualified electrical technician. Prior to commissioning, an inspection and testing of the electrical installation must be carried out in accordance with ČSN 33 1500. KORAFLEX Energy FVE convectors are powered with 230V alternating current mains
electricity. Therefore the electric branch must be equipped with a residual current device with a tripping current of 30 mA. These trench heaters are to be used solely in dry environments, and only for heating.
RAB 21-DC or RDG 160T thermostat function description
Trench heater output is controlled by fan speed and the flow of heating / cooling medium through the exchanger. The control voltage is 24 V. The RAB 21 DC or RDG 160T Siemens thermostats control the heating medium valve with a thermoelectric actuator, and in addition control fan speed with a control voltage of 0–10V DC. Fan speed may be controlled automatically by the thermostat, or manually in three speed settings. Speed rating is set at a control signal size of 7 V. Fans may be blocked by a temperature sensor (see regulation accessories). Fans start rotating when the temperature of the heating medium exceeds 37 °C. For cooling trench heaters it is recommended to use a second temperature sensor, actuated when the temperature drops below 15 °C. Temperature sensors are available as optional accessories.
Function description with BMS (Building Management System)
The BMS central control system may be used to control trench heaters. One BMS control output directly controls the opening / closing of valves and the other 0–10 V DC output controls fan speed. Rated heat output of trench heaters is achieved at 7 V DC. Valves and fans are supplied with 24 V DC.
Using the KNX system, trench heaters may be controlled with the RDG 160KN thermostat. The thermostat communicates with the KNX system, which transmits and receives data for the trench heater.
REGULATION AND ACCESSORIES
Lockshield - optional accessory | Thermostatic valve - optional accessory |
• straight • order code: | • straight or corner • order code: straight thermostatic valve: REG-TVS |
Brass elbow - optional accessory |
Flexible connecting hose - optional accessory |
• ½"×½" 90° without rim • order code: REG-E90 | • stainless steel mesh • order code (10 cm): REG-F10 • order code (12 cm): REG-F12 • order code (30 cm): REG-F3 |
Thermoelectric actuator TEP 24 - optional accessory |
Junction box - optional accessory |
• reset time: 4 min. • supply voltage: 24 V DC • order code (2.5 m cable): REG-TEP24-250 | • embedded in wall (60 W, 100 W and 150 W) • order code: REG-IB
|
R-Box - optional accessory |
Temperature sensor NTC - optional accessory |
• combined with the power supply it creates the control voltage for the fan • order code: REG-RBOX17 | • temperature sensor situated on the exchanger blocks the fan until 2 temperature sensors – one for each circuit • order code: REG-S-NTC
Temperature sensor NTC is delivered separately to the trench heater. In case of a |
Electronic room thermostat with LCD display | Electronic room thermostat with LCD display |
• for 2 and 4 pipe heating systems • order code: REG-RDG160T | • for 2 and 4 pipe heating systems • 7-day time program with 8 programmable timers • order code: REG-RDG160KN |
For correct operation, the thermostat must be set according to LICON operating instructions included in the thermostat packaging. The thermostat is supplied pre-set for 2-pipe heating systems.
Manual room thermostat |
QAA32 external room temperature sensor - optional accessory |
• for 2-pipe heating systems • order code: REG-RAB21DC | • for measuring temperature in heating • order code: REG-S-QAA32 |
For SIEMENS RDG 160T or SIEMENS RAB21-DC thermostat-controlled FVO, F2V, F4V trench heaters - heating or cooling | For BMS controlled trench heaters - heating and cooling |
The RDG 160T thermostat is pre-set for 2-pipe heating systems. For alternative methods of heating, the SIEMENS RDG 160T or RAB21-DC thermostats must be set according to the instructions enclosed, or see downloads.
FVE trench heater basic wiring diagrams | FVE trench heater with SIEMENS RDG 160T or RAB21-DC thermostat controlled trench heater basic wiring diagrams |
The RDG 160T thermostat is pre-set for 2-pipe heating systems. For alternative methods of heating, the SIEMENS RDG 160T or RAB21-DC thermostats must be set according to the instructions enclosed, or see downloads.
The RDG 160T thermostat is pre-set for 2-pipe heating systems. For alternative methods of heating, the SIEMENS RDG 160T or RAB21-DC thermostats must be set according to the instructions enclosed, or see downloads.